Bittern Earthmoving PTY LTD
O'Higgins Region, CL
@bittern-earthmoving-pty-ltd-1666499844483
Quick actions
SKU VNQXT-7896
Csbattery 12V 200ah VRLA Backup Battery for UPS/Emergency/Security/Light/LED-Lam
gb12-200
Lead-Acid Batteries
Price on request
No public price on this one — ask the supplier for a quote.
Details
GB SERIES SEALED FREE MAINTENANCE VRLA AGM BATTERY
Voltage: 12V
Capacity: 12V15Ah~12V250Ah
Designed floating service life: 8-10 years @ 25 °C/77 °F.
Summary for solar agm battery
CSBattery GB series lead acid batteries are designed to have a large amount of stored current discharged between charging sessions, with very heavy non-porous battery plates to withstand repeated major discharging and charging cycle. The CSBattery VRLA AGM battery uses a different chemistry for the plates active paste material, and a slightly stronger electrolyte than normal battery electrolyte, thus the GB range features 30% higher cyclic life with 10 years of float life when compared to the other standard Duration range.
Features and Advantages for sealed free maintenance lead acid battery
30% more cyclic life through innovation at the PAM additives
Long life expectancy of 10 years in floating condition
Thick flat plate with high Tin low Calcium alloy
Wide operating temperature range from -20 °C to 50°C
3% Low self-discharge rate
Very good deep cycle performance: up to 700 cycles @50% DOD
Excellent deep discharge recovery capability
Construction for VRLA AGM battery
Positive plate - Thick high Sn low Ca grid with special paste
Negative plate - Balanced Pb-Ca grid for improved recombination efficiency
Separator - Advanced AGM separator for high pressure cell design
Electrolyte - Dilute high purity sulfuric acid
Battery container and cover -Fire resistance ABS, water proof
Pillar seal - Two layers epoxy resin seal
Relief valve - Complete with integrated flame arrestor
Applications for VRLA SMF battery
Electric Powered Vehicles, Golf Cars and Buggies, Wheel Chairs, Power Tools, Electric Powered Toys, Control System, Medical Equipments, UPS systems, Inverter systems, Servers, Telecom, Emergency systems, Security systems, and so on.
Charging voltage and settings for Sealed MF VRLA AGM battery
l . Constant voltage charging is recommended
2. Recommended float charge voltage: 2.27V/cell @20~25°C
3. Float voltage temperature compensation: -3mV/°C/cel l
4. Float voltage range: 2.27 to 2.30 V/cell @ 20~25°C
5. Cyclic application charge voltage : 2.40 to 2.47 V/cell @ 20~25°C
6. Max. charge current allowable : 0.25C
-------------------------------------------------------------------------------------------------
Csbattery 12V 200ah VRLA Backup Battery for UPS/Emergency/Security/Light/LED-Lamp
GB12G-200A
Nominal Voltage 12V (6 cells per unit)
Design Floating Life @ 25ºC 15 Years
Nominal Capacity @ 25ºC 10 hour [email protected],10.8V 200Ah
Capacity @ 25ºC 20 hour rate (11.0A, 10.8V) 220Ah
5 hour rate (35.4A, 10.5V) 177Ah
1 hour rate (132A,9.6V) 132Ah
Internal Resistance Full Charged Battery@ 25ºC ≤2.5mΩ
Ambient Temperature Discharge -20ºC~60ºC
Charge -10ºC~60ºC
Storage -20ºC~60ºC
Max.Discharge Current @ 25ºC 1200A(5s)
Capacity affected by Temperature (10 hour ) 40ºC 105%
25ºC 100%
0ºC 85%
-15ºC 65%
Self-Discharge@25ºCper Month 3%
Charge (Constant Voltage) @ 25ºC Standby Use Initial Charging Current Less than 50A Voltage 13.6-13.8V
Cycle Use Initial Charging Current Less than 50A Voltage 14.4-14.9V
Dimension (mm*mm*mm) Length 522±1 * Width 240±1 * Height 219±1 (Total Height 224±1)
Weight (kg) 58.7±3%