Shang Hai Shi, CN
SKU sis
DO Signal (SIS) Input 24V DC 5A Safety Relay
sis signal
Price on request
No public price on this one — ask the supplier for a quote.
Details
DO SIS Signal Input 24V DC 5A Safety Relay
These safety relay are suitable for the application of E-Stop button, safety gate and DO signal from SIS, with several contacts output.
The emergency stop safety relay can be operated in single or double channel mode, manual or automatic reset, and with the function of monitoring the short circuit between channels.
Features & Advantages of DO Signal (SIS) Input 24V DC 5A Safety Relay
Several contacts output
Low start-up inrush current
Parameter of DO Signal (SIS) Input 24V DC 5A Safety Relay
CZSR8001-3A1B
CZSR8001-2A2B
Supply voltage
24V DC
24V DC
Voltage tolerance
0.85~1.1
0.85~1.1
Current consumption
≤90mA (24V DC)
≤90mA (24V DC)
Input current
≤50mA (24V DC)
≤50mA (24V DC)
Cable resistance
≤15Ω
≤15Ω
Input devices
DO signals
DO signals
Number of contacts
3NO+1NC
2NO+2NC
Contact material
AgSnO2 + 0.2 µm Au
AgSnO2 + 0.2 µm Au
External contact fuse protection
10A gL/gG NEOZED (NO);
10A gL/gG NEOZED (NO);
6A gL/gG NEOZED (NC)
6A gL/gG NEOZED (NC)
Utilisation category
In accordance with EN60947-5-1:
In accordance with EN60947-5-1:
AC-15, 5A/230V; DC-13, 5A/24V
AC-15, 5A/230V; DC-13, 5A/24V
Switch-on delay
≤300ms
≤300ms
Delay-on de-energisation
≤30ms
≤30ms
Recovery time
≤100ms
≤100ms
Supply short interruption
20ms
20ms
EMC
EN60947, EN61000-6-2, EN61000-6-4
EN60947, EN61000-6-2, EN61000-6-4
Vibration
Vibration frequency: 10Hz~55Hz;
Vibration frequency: 10Hz~55Hz;
Vibration amplitude: 0.35mm
Vibration amplitude: 0.35mm
Ambient temperature
-20℃~+60℃
-20℃~+60℃
Storage temperature
-40℃~+85℃
-40℃~+85℃
Relative humidity
10%~90%
10%~90%
Overvoltage category
Ⅲ
Ⅲ
Pollution degree
2
2
Rated insulation voltage
250V AC
250V AC
Rated impulse voltage
6000V (1.2/50us)
6000V (1.2/50us)
Dielectric strength
1500V AC, 1min
1500V AC, 1min
Clearance and creepage distance
In accordance with EN 60947-1
In accordance with EN 60947-1
Safety integrity level
SIL3
SIL3
Performance level
PLe
PLe
Category
Cat.4
Cat.4
Now the price of intrinsic safety barrier is reasonable, if you have needs, please contact us.