Modbus RTU and Porfibus
Ⅰ、Bus setting (only for Modbus, Profibus bus products, others do not have this option)
When the actuator is controlled by Profibus or Modbus fieldbus , you need to enter this item for pre-setting. If you are using a dual channel redundancy configuration, you need to set the I channel and II channel address, otherwise you only need to set the I channel address. The channel address refers to the identity code that can be recognized by the master system (master station) and itself when the bus is controlled.
Note: After the local address is reset, the actuator must be powered off first, and then re-powered to ensure Profibus or Modbus control is working properly.
In the [6] menu, use the “Up” button or “Down button” to select the “Bus Settings” item and press the “Enter” button to display the contents of the [16] menu.
I. Channel address (only for Modbus, Profibus products,
others do not have this option)
In the menu of [16], after selecting the “I channel address” item with “Upward key” or “Down shift key”, the previously set address value will be displayed on the right side of the line. Use the "plus" and "minus" keys to select the desired value from 1 to 126 and use the "confirm" key to save your changes.
2.Channel address (only for Modbus, Profibus products,
others do not have this option)
In the menu of [16], after selecting the "II channel address" item with "Upward key" or "Down shift key", the previously set address value will be displayed on the right side of the line. Use the "plus" and "minus" keys to select the desired value from 1 to 126 and use the "confirm" key to save your changes.
3.Baud rate (only for Modbus bus products, others do not have this option)
The baud rate is the number of bits of data transferred per second on the bus control loop, usually expressed in KB/S (kilobits per second).
In the menu of [16], after selecting the “Baud Rate” item with “Up Move Key” or “Down Shift Key”, the previously set actuator address value will be displayed on the right side of the line. Use the "Add" and "Subtract" keys to select the desired value from 0.3 to 38.4 KB/S and save the changes with the "Confirm" button.
4.Parity (applicable only to Modbus bus products, others do not have this option)
In the menu of [16], after selecting the “Parity” item with “Up” or “Down”, the right side of the line will display the value of the previously set check digit (“odd” or "even" or "none"). Use the "plus" and "minus" keys to select the desired value and the "confirm" key to save the selected modification
5.Bus ESD (only for Modbus bus products, others do not have this option)
"bus ESD" signal. There are two sub-items in the “Bus ESD” option, where “Prohibited” refers to not using the bus ESD function; “Allow” refers to the ESD movement in the menu of [14] to the determined position.
In the menu of [16], after selecting the “Bus ESD” item with “Up” or “Down”, the previously set ESD function (“Allow” or “Disable”) will be displayed on the right side of the line. . Use the "plus" and "minus" keys to select the desired value and the "confirm" key to save the selected modification.
6.Lost time (only for Modbus bus products, others do not have this option)
The lost time is the allowable time for the actuator to receive the bus signal. If the bus signal is not received beyond this time, it is determined that the bus signal is lost. At this time, the actuator will operate according to the requirements set in the "Drug Motion" item in the [2] menu.
In the menu of [16], after selecting the “Destination Time” item with “Up Move Key” or “Down Shift Key”, the previously set time of the lost time will be displayed on the right side of the line. Use the "plus" and "minus" keys to select the desired value from 1 to 255S and save the changes with the "confirmation key".
7.Auxiliary remote control (only for Modbus bus products, others do not have this option)
The auxiliary remote control is to select whether the terminals 22, 23, and 24 in the terminal table of the actuator are used as the normal status signal input terminal or as the remote open control signal input terminal. If it is the input signal of the normal status signal, the terminal will feed back to the primary station when it is at a high level (positive voltage), and vice versa. If the control signal input is turned on as a remote, the terminal is at a high level (positive voltage), indicating that the actuator has been requested to receive a control command that requires an open action.
In the menu of [16], after selecting the “Auxiliary Remote Control” item with “Up Move Key” or “Down Shift Key”, the previously set value will be displayed on the right side of the line. Use the "Plus" and "Subtract" keys to select the desired value and the "Confirm" key to save your changes.
8.Auxiliary ESD (only for Modbus bus products, others do not have this option)
The auxiliary ESD is the terminal of the actuator selection. The terminal No. 12 is used as the normal status signal input terminal or as the remote control signal input terminal. If it is the input signal of the normal status signal, the terminal will feed back to the primary station when it is at a high level (positive voltage), and vice versa. If the control signal input is turned off as a remote, the terminal is at a high level (positive voltage), indicating that the actuator has been requested to receive a control command requesting an ESD action.
In the menu of [16], after selecting the “Auxiliary ESD” item with “Up” or “Down”, the previously set value will be displayed on the right side of the line. Use the "Add" and "Subtract" keys to select the desired value and the "Confirm" key to save your changes